Loop Burnout Alarm Section 4-12
Initial Setting Level
3. Press the U Key to set the parameter to 12.
4. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
Advanced Function Setting Level
5. Press the D Key to enter the password (−169), and move from the initial
setting level to the advanced function setting level.
Advanced Function Setting Level
6. Select the LBA Detection Time parameter by pressing the M Key.
7. Press the U Key to set the parameter to 10.
Advanced Function Setting Level
8. Select the LBA Level parameter by pressing the M Key.
9. Press the U Key to set the parameter to 8.0. (The default is 8.0.)
Advanced Function Setting Level
10. Select the LBA Band parameter by pressing the M Key.
11. Press the U or D Key to set the parameter to 3.0. (The default is 3.0.)
Initial Setting Level
12. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
Operation Level
13. Press the O Key for at least one second to move from the initial setting
level to the operation level.
alt1
12
amov
0
Move to Ad-
vanced Function
Setting Level
init
off
Parameter
Initialization
lba
0
LBA Detection
Time
C
lba
10
C
lbal
8.0
LBA Level
C
lbal
8.0
C
lbab
3.0
LBA Band
C
lbab
3.0
in-t
5
Input Type
C
25
100
PV/S
P

Table of Contents