212
Initial Setting Level Section 5-7
• This parameter sets the upper and lower limit values of transfer outputs.
â–  Related Parameter
Transfer output type (initial setting level): Page 210
This parameter selects the output type for linear current outputs.
Note Even when control output 1 is used as a control output or a simple transfer
output, 0 to 20 mA can be used.
â–  Related Parameter
Transfer output type (initial setting level): Page 210
tr-h Transfer Output Upper Limit
There must be a transfer output or a
current output.
The transfer output type must not be
set to OFF.
tr-l Transfer Output Lower Limit
Function
Setting
Transfer output
type
Setting range Default Unit
Transfer
output lower
limit
Transfer
output upper
limit
Set point SP lower limit to SP upper limit SP lower limit SP upper limit EU
Set point during
SP ramp
SP lower limit to SP upper limit
PV Temperature Input setting range lower limit
to input setting range upper
limit
Input setting
range lower
limit
Input setting
range upper
limit
Analog Analog scaling lower limit to
analog scaling upper limit
Scaling lower
limit
Scaling upper
limit
MV monitor
(heating)
Standard −5.0 to 105.0 0.0 100.0 %
Heating/
cooling
0.0 to 105.0
MV monitor
(cooling)
0.0 to 105.0
See
See
o1-t Linear Current Output
Control output 1 must be a current
output.
Linear current
output
Default
4-20: 4 to 20 mA
0-20: 0 to 20 mA
4-20
Setting
See
See

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals