Advanced Function Setting Level Section 5-8
This parameter selects the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Condition A
Control started (including power ON), and set point, alarm value (alarm
value upper/lower limit), or input shift value (upper/lower-limit temperature
input shift value) changed.
Condition B
Power ON
The following example shows the reset action when the alarm type is
lower-limit alarm with standby sequence.
Related Parameters
Alarm 1 to 3 type (initial setting level): Page 207 to 209
Alarm 1 to 3 latch (advanced function setting level): Page 227
rest Standby Sequence Reset
Alarm 1 to 3 type must be 5, 6, 7, 10,
or 11.
Setting range Default
a: Condition A, b: Condition B a
Function
Alarm
(after change)
Alarm
SP change
Condition A only
Condition A
only
Alarm hysteresis
: Standby sequence canceled
: Standby sequence reset
Alarm output:
Condition A
Alarm output:
Condition B
Setting
See
See