6 Parameters
6 - 76
E5@C-T Digital Temperature Controllers User’s Manual (H185)
calb
Motor Calibration A Position-proportional Model must be used.
The Motor Calibration parameter is used to calibrate the valve position and automatically set
the travel time from completely open to completely closed. You can then check the valve
opening with the Valve Opening Monitor parameter.
If you set the Motor Calibration parameter to ON, the valve will open completely and close
completely, and then the setting of the parameter will change to OFF when the measure-
ment has been completed. “ERR” will be displayed if any of the following errors occurs dur-
ing execution. If an error occurs, check the wiring and other factors and execute motor
calibration again.
The potentiometer input value does not change or changes backward between
completely open and completely closed because the wiring is wrong.
The value of the potentiometer input is incorrect because of a broken wire, noise, or other
factor.
* Do not change to any other parameter during calibration.
z Related Parameters
Travel Time (Initial Setting Level): Page 6-76
mot
Travel Time A Position-proportional Model must be used.
The Travel Time parameter is set to the time from when the valve is completely open until
it is completely closed.
This parameter is set automatically when motor calibration is executed. There is normally
no need to change it manually.
To use the results of automatic motor calibration calculations with another Digital
Controller, set the following parameters as a set: Travel Time, Valve Completely Closed
Position, Valve Completely Open Position, and Potentiometer Specification Setting.
However, these settings will depend on the equipment. When precise operation is
required, execute motor calibration separately for each piece of equipment.
z Related Sections
5-21 Controlling Valves (Can Be Used with a Position-proportional Model) (page 5-79)
z Related Parameters
Motor Calibration (Initial Setting Level): Page 6-76
vl-c
Valve Completely Closed Position A Position-proportional Model must be used.
Function
Operation
See
See
Function
Operation
Setting range Unit Default
1 to 999 Seconds 30
See
See

Table of Contents

Other manuals for Omron E5CC-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC-T and is the answer not in the manual?

Omron E5CC-T Specifications

General IconGeneral
BrandOmron
ModelE5CC-T
CategoryTemperature Controller
LanguageEnglish

Related product manuals