E5CK-T E5CK-T
185
J PARAMETERS AND MENUS
All functions selected with the Controller in setup or expansion mode or all optional functions of the Process Controller may not be
displayed.
Note: All references to Heater Burnout Alarm Function and position-proportional apply only to E5EK/AK-T and are not applicable to
E5CK-T.
Protect Mode
The protect function is for preventing unwanted modification
of parameters and switching between run and reset operation
or auto and manual operation.
Manual Mode
In this mode, the Controller can be switched to manual
operation. The manipulated variable can be manipulated
manually only in this mode.
Level 0 Mode
Set the Controller to this mode during normal operation. In
this mode, you can change the set point and pattern during
operation, and execute step operation (e.g. advance). You
can only monitor (not change) the process value, step No.,
standby time, pattern elapsing time, pattern execution count,
and manipulated variable.
Program Mode
This is the programming mode. In this mode, you can set the
number of steps used in each pattern, pattern execution
count, alarm values, set points for each step, step time, and
time signals for two steps.
Level 1 Mode
This is the main mode for adjusting control. In this mode, you
can execute AT (auto-tuning), set up the control period,
change PID parameters, and set alarm values.
Level 2 Mode
This is the auxiliary mode for adjusting control. In this mode,
you can set the parameters for limiting the manipulated
variable, switch between the remote and local modes, and
set the loop break alarm (LBA), alarm hysteresis, and the
digital filter value of inputs.
Setup Mode
This is the mode for setting the basic specifications. In this
mode, you can set parameters that must be checked or set
before an operation such as the input type, scaling, output
assignments, and direct/reverse operation.
Expansion Mode
This is the mode for setting expanded functions. In this
mode, you can set SP setting limiter, switching between
advanced PID control or ON/OFF control, program time unit,
selection of step time/rate of rise, time unit of ramp rise rate,
and the time for automatic return to the monitoring display.
Option Mode
This is the mode for setting optional functions. You can select
this mode only when an option board is mounted in the
Controller. In this mode, you can set the communications
conditions, transfer output and event input parameters to
match the type of option board mounted in the Controller.
Calibration Mode
This mode is provided so that the user can calibrate inputs
and output. When calibrating input, the selected input type is
calibrated. Whereas, transfer output can be calibrated only
when the communications board (E53-CKF) is set in the
Controller.