6 Programless Communications
6 - 48
E5@C Digital Temperature Controllers Communications Manual (H175)
(3) Change a set point.
Enter 100 (64 hex) as the value for D017 (SP) in the Watch Tab Page and press the Enter
Key. Confirm that D000 (Response Flag) remains at 1 (Enable Writing) and that the SV
Display on the No. 0 E5CC changes to 100.
Stopping the E5CC Controller
(1) Run the No. 0 Controller.
Change the RUN/STOP parameter (r-s) in the operation level of the E5CC to RUN (run).
(2) Switch the No. 0 Controller to STOP.
Confirm that D015 (Request Flag) in the Watch Tab Page is 0001 hex (Enable Writing),
enter 0101 hex (Stop) for D016 (Operation Command Code), and press the Enter Key.
D016 will change to 0000 hex, D000 (Response Flag) will remain at 0001 hex (Enable
Writing), and “STOP” will be displayed on the No. 0 E5CC.
Confirm this for the No. 1 and No. 2 Controllers as well.
For details on other operation command codes, refer to 6-3-4 Operation Command Codes.