3 Communications Data for CompoWay/F
3 - 4
E5@C Digital Temperature Controllers Communications Manual (H175)
Variable
type
Address Parameter name Setting (monitor) value Level
C1 (81) 0016 Integral Time Standard, heating/cooling, or close
position-proportional control:
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Floating position-proportional control:
H'00000001 to H'0000270F
(1 to 9999: Integral/derivative time unit is 1 s.)
(0.1 to 999.9: Integral/derivative time unit is 0.1 s.)
Adjustment
C1 (81) 0017 Derivative Time H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81) 0019 Dead Band H'FFFFF831 to H'0000270F
(199.9 to 999.9 for temperature input)
(19.99 to 99.99 for analog input)
C1 (81) 001A Manual Reset
Value
H'00000000 to H'000003E8 (0.0 to 100.0)
C1 (81) 001B Hysteresis
(Heating)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81) 001C Hysteresis
(Cooling)
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81) 001D Heater Burnout
Detection 2
H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81) 001E HS Alarm 1 H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81) 001F HS Alarm 2 H'00000000 to H'000001F4 (0.0 to 50.0)
C1 (81) 0020 Soak Time H'00000001 to H'0000270F (1 to 9999)
C1 (81) 0021 Wait Band H'00000000 (0): OFF
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C1 (81) 0022 MV at Stop Standard Models
Standard control:
H'FFFFFFCE to H'0000041A (5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (105.0 to 105.0)
Position-proportional Models
Close position-proportional control with the Direct
Setting of Position Proportional MV parameter set to
ON:
H'FFFFFFCE to H'0000041A (5.0 to 105.0)
Floating position-proportional control or the Direct
Setting of Position Proportional MV parameter set to
OFF:
H'FFFFFFFF to H'00000001 (1 to 1)
C1 (81) 0023 MV at PV Error

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20