- 67 -
6.
EN/IEC Standards
5. Output (Built-in Relay) Life Expectancy
The insulation system between the power supply circuit and output terminals provides
basic insulation.
Therefore connect the output terminals only to circuits without accessible conductive
parts. If a connection to Safety Extra Low-Voltage (SELV) circuits is desired,
supplementary insulation must be provided.
Use crimp type cable lug terminals with insulating sleeves for wiring.
Be sure to mount a surface-mounting model (H5S- FB ) in a enclosure.
The derating curve shows the load current as a sum of both outputs [A] vs. the
ambient air temperature [˚C] of 2 channel types.
If wires with a temperature rating of 105 ˚C or higher are used, see the derating
curve in the Section 4, "Ratings and characteristics".
Control system Electronic
Types of automatic operation
Weekly models - Type 1BSTU
Yearly models - Type 2BSTU
Protective class
Class 0
Rated impulse withstand voltage
2500V AC
Ball-pressure test temparature (enclosure material)
125˚C
0
-10 0 4025 55
20
30
Ambient air temperature C)
Load current as
sum of 2 outputs (A)
<2 channel type>
Mechanical life expectancy at 20˚C 100,000 operations min.
Electrical life expectancy at 20˚C
• 50,000 operations min. for a resistive load of 15 A at 250 VAC
• 50,000 operations min. for a resistive load of 10 A at 30 VDC
50,000 operations min. for an inductive load (cos = 0.7) of 10 A at 250 VAC
• 50,000 operations min. for a motor load of 1 HP at 250 VAC
• 50,000 operations min. for a lamp load of 100 W at 100 VAC
• 10,000 operations min. for a lamp load of 300 W at 100 VAC
<4 channel type>
Mechanical life expectancy at 20˚C 100,000 operations min.
Electrical life expectancy at 20˚C
• 50,000 operations min. for a resistive load of 3 A at 250 VAC
• 50,000 operations min. for a resistive load of 3 A at 30 VDC