Page #29 background imageLoading...
Page #29 background image
21
3-2 Setting Mode
3-2-1 Selecting Setting Mode
The K3NX in RUN mode will go into setting mode if the Mode Key is pressed for
1 s minimum.
The K3NX in setting mode will go into RUN mode if the Escape Key is pressed.
RUN mode
Press the Mode and Shift Keys
while turning the K3NX on.
Power On
Press the Escape and Up
Keys for 1 second.
Maintenance mode
RUN mode
1 second
Setting mode
Protect mode
The menu in each mode changes whenever the Mode Key is pressed.
If the Mode Key is pressed for more than one second while a menu is dis-
played, a parameter will be displayed.
The parameter changes whenever the Mode Key is pressed.
If the Shift Key is pressed while a parameter is displayed, the parameter will be
ready to change.
Press the Up Key to change parameters.
The digit of a set value is selected with the Shift Key and changed with the Up
Key.
The PROG indicator is lit while a menu or parameter is displayed.
The PROG indicator flashes during a set value change.
Note If the input range is changed, all the other parameters will be set to default val-
ues. Therefore, set the input range first.
Setting Mode
Section 3-2
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr

Table of Contents

Other manuals for Omron K3NX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron K3NX and is the answer not in the manual?

Omron K3NX Specifications

General IconGeneral
BrandOmron
ModelK3NX
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals