34
Power Supply Frequency
• Set the number of sampling times in the setup menu according to the power
supply frequency in order to shut off inductive noise that may be generated
from the power supply.
Setting Unit Number of sampling
times
Default
50/60 Hz 50: 12.5 times/second
60: 15 times/second
50
Follow the steps described below to set the power supply frequency to 60 Hz.
Set Value LED Display Model Basic Model
1, 2, 3... 1. Press the Mode Key for more than one second while the setup setup menu
is displayed. The inĆt input range setting will appear.
Set Value LED Display Model Basic Model
2. Press the Mode Key to display the fre power supply frequency setting.
Set Value LED Display Model Basic Model
3. Press the Shift Key to display the prior set value 50 for changing. The PROG
indicator will flash.
Set Value LED Display Model Basic Model
4. Press the Up Key to display the set value 60. The displayed value will be
validated automatically if no change is made for five seconds. The fre pow-
er supply frequency setting will be displayed again.
Set Value LED Display Model Basic Model
fre
FUNCTION
SETTING
SETTING
EXAMPLE
Setting Mode
Section 3-2