EasyManua.ls Logo

Omron RX - Page 157

Omron RX
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-52
4-2 Function Mode
4
Functions
RUN Time/Power ON Time Exceeded
If the total RUN time of the Inverter exceeds the time set in ON time setting b034, a RUN/Power
ON 'time exceeded' (RNT/ONT) signal is output.
RUN Time Exceeded (RNT)
Allocate 11 (RNT) to any of multi-function output terminals 11 to 15 (C021 to C025) or the relay
output terminal (C026).
Set a time in RUN time/Power ON time setting b034.
Power ON Time Exceeded (ONT)
Allocate 12 (ONT) to any of multi-function output terminals 11 to 15 (C021 to C025) or the relay
output terminal (C026).
Set a time in RUN time/Power ON time setting b034.
Rotation Direction Limit Selection
Limits motor rotation directions.
Enabled in either "control circuit terminal block" or "Digital Operator" control mode.
When a limited RUN command is input, the Digital Operator displays .
Parameter No. Function name Data Default setting Unit
b034
RUN time/Power ON
time setting
0.: Does not operate.
0
1. to 9999.:
Set in increments of 10 hours.
1000 to 6553:
Set in increments of 100 hours.
(100000 to 655300 hours)
Related functions C021 to C025, C026, d016, d017
OkOkOkO
Parameter No. Function name Data Default setting Unit
b035
Rotation direction limit
selection
00: Forward and Reverse are enabled.
01: Only Forward is enabled.
02: Only Reverse is enabled.
00

Table of Contents

Related product manuals