5-2 Warning Function
5
Maintenance Operations
5-2 Warning Function
•The following table shows the details of warning display and parameter correction.
Warning display Target code Condition Base code
001/201 Frequency upper limit A061/A261 >
Maximum frequency
A004/A204/A304
002/202 Frequency lower limit A062/A262 >
004/204/304 Base frequency A003/A203/A303
*1
>
005/205/305
Output frequency F001, Multi-step speed reference 0 A020/
A220/A320
*2
>
006/206/306 Multi-step speeds 1 to 15 A021 to A035 >
009 Orientation speed setting P015 >
012/212 Frequency lower limit A062/A262 >
Frequency upper limit
A061/A261
015/215
Output frequency F001, Multi-step speed reference 0 A020/
A220
*2
>
016/216 Multi-step speeds 1 to 15 A021 to A035 >
019
Frequency upper limit A061/A261
<
Orientation speed
P015
021/221 <
Frequency lower limit
A062/A262
025/225
Output frequency F001, Multi-step speed reference 0 A020/
A220/A320
*2
<
031/231 Frequency upper limit A061/A261 <
Starting frequency
b082
032/232 Frequency lower limit A062/A262 <
035/235/335
Output frequency F001, Multi-step speed reference 0 A020/
A220/A320
*2
<
036 Multi-step speeds 1 to 15 A021 to A035 <
037 Jogging frequency A038 <
085/285/385
Output frequency F001, Multi-step speed reference 0 A020/
A220/A320
*2
< >
Jump frequency 1/2/3
± Jump width
A063 ± A064
A065 ± A066
A067 ± A068
*3
086 Multi-step speeds 1 to 15 A021 to A035 < >
*1. In this case, the base frequency is rewritten when correcting parameters. Change the data to a correct value
if a warning occurs. Otherwise, the motor may burn out depending on the value.
*2. Checks even if the frequency reference selection (A001) is set other than to the Digital Operator (02).
*3. The jump frequency is rewritten into the value of the subtraction of the jump width (lower limit) from the jump
frequency.