4-60
4-2 Function Mode
4
Functions
Momentary Power Interruption Non-stop Function
•After the power is shut off during operation, this function decelerates the Inverter to a stop while
keeping the voltage below the overvoltage level.
•You can select from three modes in momentary power interruption non-stop selection b050.
Parameter No. Function name Data Default setting Unit
b050
Selection of non-stop
function at momentary
power interruption
00: Disabled
01: Enabled
02: DC voltage constant control (without
recovery)*
5
03: DC voltage constant control (with
recovery)*
5
00
b051
Starting voltage of non-stop
function at momentary
power interruption
*4
0.0 to 1000. 220/440 V
b052
Stop deceleration level of
non-stop function at
momentary power
interruption
*1
*4
0.0 to 1000. 360/720 V
b053
Deceleration time of non-
stop function at momentary
power interruption
*3
0.01 to 3600. 1.00 s
b054
Deceleration starting width
of non-stop function at
momentary power
interruption
*3
0.00 to 10.00 0.00 Hz
b055
Proportional gain setting of
non-stop function at
momentary power
interruption
0.00 to 2.55:
Proportional gain for DC voltage constant
control
(b050 = 02, 03 only)
0.20
b056
Integral time setting of non-
stop function at momentary
power interruption
0.000 to 9.999/10.00 to 65.53:
Integral time for DC voltage constant
control
(b050 = 02, 03 only)
0.100 s