If the above maximum rated carrier frequency and the derating value at 15 kHz are exceeded, the
Inverter may be damaged and/or the service life may be shortened.
Parameter Initialization
You can initialize the rewritten set values and reset to the factory default.
You can clear trip data.
You cannot clear the P100 to P131 set values, RUN time, or power ON time.
11 kW 12 90% (41.4 max.) 15 100%
15 kW 12 95% (60.8 A max.) 14 95% (30.4 A max.)
18.5 kW 10 90% (68.4 A max.) 10 90% (34.2 A max.)
22 kW 7 70% (66.5 A max.) 6 75% (36.0 A max.)
30 kW 5 80% (96.8 A max.) 10 75% (43.5 A max.)
37 kW 10 75% (108.7 A max.) 8 80% (60.0 A max.)
45 kW 5 70% (127.4 A max.) 9 75% (68.2 A max.)
55 kW 5 70% (154 A max.) 6 60% (67.2 A max.)
75 kW  6 85% (126.7 A max.)
90 kW  4 75% (132.0 A max.)
110 kW  6 70% (151.9 A max.)
132 kW  3 60% (156.0 A max.)
Voltage 200-V class 400-V class
Capacity Max. fc (kHz) Derating at fc = 15 kHz Max. fc (kHz)
Derating at fc = 15 kHz
(75 to 132 kW is for 10 kHz)
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
60
55
100
95
90
85
80
75
70
65
0.5 2 4 6 8 10 12 1514
200-V class 400-V class
Output current derating
Carrier frequency (kHz)
Output current derating
Carrier frequency (kHz)
15 kW
37 kW
30 kW
11 kW
18.5 kW
22 kW
45,55 kW
15 kW
22 kW
18.5 kW
37 kW
55 kW
30 kW
75 kW
90 kW
110 kW
132 kW
45 kW
Parameter No. Function name Data Default setting Unit
b084 Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
00
b085
Initialization parameter
selection
00: Do not change 00