4-118
4-2 Function Mode
4
Functions
Stabilization Parameter
•This function adjusts to reduce motor hunting.
•In case of motor hunting, check whether motor capacity H003/H203 and motor pole number
selection H004/H204 match your motor. If they do not, match them. If the motor's primary
resistance is smaller than that of the standard motor, increase the H006/H206/H306 set value
gradually. To run a motor with a capacity larger than the Inverter's rated capacity, reduce the set
value.
•Other than this function, the following methods are suggested to reduce hunting:
Lower the carrier frequency (b083). (Refer to page 4-65.)
Lower the output voltage gain (A045). (Refer to page 4-24.)
Parameter No. Function name Data Default setting Unit
H006/H206/H306 Stabilization parameter
0. to 255.:
If hunting occurs, adjust the set value.
100.
A045 Output voltage gain
20. to 100.:
If hunting occurs, reduce the set value.
100 %
b083 Carrier frequency
0.5 to 15.0:
If hunting occurs, reduce the set value.
5.0 kHz