EasyManua.ls Logo

Omron RX - Page 339

Omron RX
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-10
6-1 Inspection and Maintenance
6
Inspection and Maintenance
Note 1: For output voltage, use
a measurement device
that displays effective
values of fundamental
wave. For current and
electric power, use a
measurement device
that displays all
effective values.
Note 2: The Inverter output
waveform, under PWM
control, has a margin of
error, especially at a
low frequency.
Note 3: General-purpose
testers are not
applicable because of
noise in many cases.
Measurement Method of Output Voltage
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
Inverter
Motor
2 W 220 kW
V
DC
Moving coil type
300 V (200-V class)
600 V (400-V class)
Diode
600 V 0.1 A min. (200-V class)
1000 V 0.1 A min. (400-V class)
Power supply
R
S
T
U
V
W
Effective value of fundamental wave VAC
V
AC = 1.1 × VDC
+
-

Table of Contents

Related product manuals