App-3
Appendix-1 Parameter List
Appendix
Basic Function Mode (F)
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
F001
Output frequency
setting/monitor
0.0/Starting frequency to 1st/2nd/3rd max.
frequency
0.0 to 100.0 (PID control enabled)
Yes Hz 4-8
F002 Acceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F202
* 2nd acceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F302
* 3rd acceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F003 Deceleration time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F203
* 2nd deceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F303
* 3rd deceleration
time 1
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
30.00 Yes s 4-8
F004
Operator rotation
direction selection
00: (Forward)
01: (Reverse)
00 No 4-9
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.