106
Frame Structure Section 7-2
Addresses
Monitored Values
■ Variable Type 80
Note If the upper limit of the displayable range is exceeded, the upper limit will be
displayed. If the lower limit is exceeded, the lower limit will be displayed.
Alarm Status The alarm status is used to read the controller status.
Alarm Cause
■ Variable Type 80
Note The run time and temperature are represented by variables 0002 and 0003,
respectively.
Address Name Data range
0000 Present input voltage 00A3 to 012C (16.3 to 30.0 V)
0001 Total current 0000 to 0190 (0.0 to 40.0 A)
0002 Run time 0000 to 03E7 (0 to 999 kh)
0003 Internal temperature FFEC to 0064 (−20 to 100°C)
Address Name Data range
0010 Present current, branch output 1 0000 to 0064 (0.0 to 10.0 A)
0011 Present current, branch output 2
0012 Present current, branch output 3
0013 Present current, branch output 4
0020 Peak output current, branch output 1 0000 to 0064 (0.0 to 10.0 A)
0021 Peak output current, branch output 2
0022 Peak output current, branch output 3
0023 Peak output current, branch output 4
Address Name Data range
1000 Voltage when abnormal voltage trip-
ping occurred
00A3 to 012C (16.3 to 30.0 V)
1001 Maximum voltage after overvoltage
alarm occurred
00A3 to 012C (16.3 to 30.0 V)
1002 Minimum voltage after undervoltage
alarm occurred
00A3 to 012C (16.3 to 30.0 V)
Address Name Data range
1010 Current when abnormal current trip-
ping occurred in branch output 1
(Redundant abnormal current tripping
for the S8M-CP04-RS only)
0000 to 0064 (0.0 to 10.0 A)
1011 Current when abnormal current trip-
ping occurred in branch output 2
(Redundant abnormal current tripping
for the S8M-CP04-RS only)
1012 Current when abnormal current trip-
ping occurred in branch output 3
(Redundant abnormal current tripping
for the S8M-CP04-RS only)
1013 Current when abnormal current trip-
ping occurred in branch output 4
(Redundant abnormal current tripping
for the S8M-CP04-RS only)