6-3 Setting and Saving Parameters
The Parameter Setting Window appears when the Support Tool starts. The
parameters can be set in this Window and the various functions can also be
selected from the Menu Bar.
Setting the
Parameters
There are two tab pages in the Parameter Setting Window: the Basic Settings
Tab Page and Branch Output Settings Tab Page. Switch between these tab
pages by clicking the corresponding tab at the bottom of the page and set the
parameters in each tab page.
The parameters set in this window are just set in the Support Tool. The edited
parameters must be downloaded to the S8M to change the S8M's parame-
ters.
Basic Settings Tab Page
(Window Displayed at
Startup)
Set the parameter under each heading. If a setting is outside of the allowed
setting range, a warning message will be displayed and the setting will not be
accepted.
Note The alarm will not be output when the alarm value is set to 0.0 kh.
Parameter Settings Reference
page
Setting range Default value
Undervoltage alarm value 18.0 to 26.4 V 20.0 V 27
Overvoltage alarm value 20.0 to 28.8 V 28.8 V 27
Over-temperature output value 25 to 80°C80°C28
Run time value 0.0 to 99.9 kh 0.0 kh (See note.) 30
▲
Click here to switch to the Branch Output Settings Tab Page.