Operation Command Section 7-8
7-8 Operation Command
This service performs operation command processing.
Service Request PDU
Service Response PDU
(1) Command Codes and Related Information
Note When a command is executed for all of the outputs, but the processing could
not be performed on one or more outputs, the processing will still be per-
formed on the other outputs. In this case, a normal response will be returned,
so read the controller status to check whether or not the outputs were actually
connected/cut off.
MRC SRC
3 0 0 5
2 2 2 2
Command
Code
Related
Info.
MRC SRC
3 0 0 5
2 2 4
Response Code
Command
code
Command content Related Information
00 Connect Each bit corresponds to a branch output.
(Multiple branch outputs can be specified.)
01: Branch output 1
02: Branch output 2
04: Branch output 3
08: Branch output 4
01 Disconnect (Cut off) Each bit corresponds to a branch output.
(Multiple branch outputs can be specified.)
01: Branch output 1
02: Branch output 2
04: Branch output 3
08: Branch output 4
02 Startup sequence Always set to 00.
03 Shutdown sequence Always set to 00.
04 Reset switch Always set to 00.
10 Clear peak output
current
Each bit corresponds to a branch output.
(Multiple branch outputs can be specified.)
01: Branch output 1
02: Branch output 2
04: Branch output 3
08: Branch output 4
11 Clear run time Always set to 00.