Seven-segment Error Codes Section 8-2
8-2 Seven-segment Error Codes
Error Display List
Operation The peak output current is not
displayed and the display
shows “- - -.”
The current may have
exceeded the measurable
range.
Clear the peak output current
in Run Mode.
18, 79
The peak output current is
higher than the abnormal cur-
rent tripping value, but the
output has not been cut off.
The S8M provides a startup
delay so that inrush currents
do not cause tripping at star-
tup. The output will thus not
be cut off at startup, but the
maximum current will be
recorded as the peak output
current.
Clear the peak output current
using the operation provided.
Thereafter, the peak output
current during normal opera-
tion will be recorded.
79, 93,
136
The output was not designed
for a current that high, but the
output is cut off as soon as
power is supplied.
The abnormal current trip-
ping type may be set to
“instantaneous.” With instan-
taneous detection, an abnor-
mal current is detected very
quickly and the output may be
cut off due to excessive cur-
rent during equipment opera-
tion.
Either change the abnormal
current tripping type from
instantaneous to standard or
increase the current tripping
value.
58
There may be a large number
of devices connected to the
output. The more devices that
are connected, the higher the
operating current.
Connect the devices to differ-
ent branch outputs and use
the S8M's startup sequence
to offset the connections to
the devices.
30, 64
Branch out-
put cutoff
The connection cannot be
reset immediately after it is
cut off (RST) is displayed.
To protect the S8M's internal
circuits, at least 15 seconds
must pass before a cut-off
output can be reset.
Press the Reset Key for at
least 3 s. “RST” should be
displayed and the cut-off out-
put can be reset after 15 sec-
onds have passed since the
cutoff.
22, 125
The output was reset, but it
was immediately cut off
again.
The original cause of the cut-
off may not have been elimi-
nated.
After resetting the error, a
large current may have flowed
again.
Eliminate the problem that
caused the cutoff and press
the Reset Key for at least 3 s.
125
Saving or
maintenance
The run time alarm was out-
put, so the equipment was
checked and other parts were
replaced, but the alarm could
not be cleared.
The S8M continues adding to
the run time. The run time
must be reset to 0 in order to
clear the alarm.
Clear the run time and then
press the Reset Key for at
least 3 s.
The alarm can also be
cleared by increasing the run
time value and then resetting.
62, 71,
125
All of the outputs were discon-
nected when the parameters
were initialized.
Initializing parameters returns
all settings to their default val-
ues. To ensure safety, all out-
puts are disconnected by
default.
The S8M will be in Setting
Mode after initializing the
parameters. Change to Test
Mode and connect the
required branch outputs.
53, 98,
133
Stage Observed problem Possible cause Remedy Reference
page
Seven-segment
display
Error
code
Meaning Probable cause and remedy
e98 E98 RAM error These are S8M system errors.
When one of these error codes is displayed, contact an OMRON rep-
resentative regarding the error.
e97 E97 EEPROM read error
e96 E96 EEPROM write error
e94 E94 A/D conversion error