Setting and Saving Parameters Section 6-3
Branch Output Settings
Tab Page (Individual
Branch Output Settings)
Note (1) The startup sequence can set delays from the point that the S8M's power
is turned ON until power is supplied at each branch output.
(2) The shutdown sequence set delays from the point that the external trip-
ping input goes ON until each branch output is cut off.
(3) The external signal input's tripping operation can be enabled or disabled
independently for each branch output.
(4) The setting ranges for the abnormal current tripping value and overcur-
rent alarm value are slightly different in the S8M models. If a value that is
Parameter Settings Reference
page
Setting range Default value
Abnormal current tripping type Standard or
instantaneous
Standard 22
Abnormal current
tripping value
S8M-CP04-R 0.5 to 4.0 A 4.0 A 22
S8M-CP04-RS 0.5 to 3.8 A 3.8 A
Overcurrent alarm type Standard or
instantaneous
Standard 25
Overcurrent alarm
value
S8M-CP04-R 0.5 to 4.0 A 4.0 A 25
S8M-CP04-RS 0.5 to 3.8 A 3.8 A
Startup sequence (See note 1.) 0 to 99.9 s 0.0 s 30
Shutdown sequence (See note 2.) 0 to 99.9 s 0.0 s 31
External tripping input (See note 3.) Enable/Disable Enable 4, 41
▲
Click here to switch to the Basic Settings Tab Page.