Clearing Errors Section 8-3
• If the overcurrent is occurring momentarily, check the abnormal current
tripping type setting on page
58. The detection of short-lived abnormal
currents can be prevented by changing the setting from instantaneous
detection (detection after 10 ms) to standard detection (detection after
80 ms).
Over-temperature Output
(A30) Displayed
When error code A30 (over-temperature) and the temperature are displayed
alternately on the seven-segment display, there are two possible causes.
Check whether the S8M's internal temperature is too high or the setting of the
over-temperature output value is too low.
Run Time Alarm (A23)
Displayed
When error code A23 (run time alarm) is displayed on the seven-segment dis-
play, check whether some component in the system requires maintenance or
there is a problem with the setting of the run time value.
• If outputting run time alarms is not required, set the alarm value to 0.0 kh.
• When you want to clear the run time, execute the clear run time operation
in Setting Mode (see page 71). The run time cannot be cleared from the
Support Tool.
Reading and Clearing Errors from the Support Tool
Select Monitor - Status or Monitor - Present Values to display the Status
Window or Present Values Window. Errors can be checked and cleared from
these windows. First identify and eliminate the cause of the error and then
click the Reset Button.
Example Error Display in the Status Window
Current when output
was cut off.
▲
Reset Button
▲
▲
Message
▲
Lit red because
the output was
cut off.