32
Shutdown Sequence Function Section 2-6
Note
(a) When operation is cut off due to an abnormal voltage (above
28.8 V), all of the branch outputs will be cut off simultaneously.
(b) The shutdown sequence function will operate on a branch output
only if the external tripping input is enabled for that branch output.
The shutdown sequence's operation can be verified in Test Mode. For
details, refer to 5-3 Checking Sequence Operation.
The shutdown sequence's operation can also be verified from the Support
Tool by clicking the Shutdown sequence Button on the Present Values
Window. (For details, refer to page 94.)
Note The shutdown sequence functions in the following processes:
Operation cut off by the external tripping input
Shutdown sequence executed by CompoWay/F command (Startup
Sequence)
Simultaneous cutoff of all outputs in Test Mode
Shutdown sequence executed from the Support Tool