68
Analog Monitor Output Chapter 5-10
5-10 Analog Monitor Output
The J7AZ incorporates analog monitor output terminals AM and AC.
These terminals have analog monitor values of output frequency or current.
Setting the Analog Monitor Output (n44 and n45)
The output frequency or current as a monitored item is set in n44.
The analog output characteristics are set as an analog monitor output
gain in n45.
Set Value
Note 1. Set the multiplication ratio based on the set value in n44.
For example, if an output of 5 V is desired at maximum frequency
(with n44 set to 0), set n45 to 0.50.
2. The maximum output voltage of the analog monitor output terminals
are 10 V.
n44 Analog Monitor Output Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Value Description
0 Output frequency (Reference: 10 V at max. frequency)
1 Output current (Reference: 10 V with rated output current)
n45 Analog Monitor Output Gain Changes during
operation
Yes
Setting
range
0.00 to 2.00 Unit of
setting
0.01 Default setting 1.00