EasyManua.ls Logo

Omron VS mini J7

Omron VS mini J7
177 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Wiring Chapter 2-2
2-2-4 Wiring around the Main Circuit
Wire Size, Terminal Screw, Screw Tightening Torque, and Molded-case
Circuit Breaker Capacities
For the main circuit and ground, always use 600-V polyvinyl chloride (PVC)
cables.
If any cable is long and may cause voltage drops, increase the wire size
according to the cable length.
3-phase 200-V AC Model
Model
CIMR-J7AZ-
Terminal symbol Terminal
screw
Screw
tightening
torque
(Nm)
Wire size
(mm
2
)
Re-
commended
wire size
(mm
2
)
Molded-
case circuit
breaker
capacity (A)
20P1 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 0.75 to 2 2 5
20P2 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 0.75 to 2 2 5
20P4 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 0.75 to 2 2 5
20P7 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 0.75 to 2 2 10
21P5 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 2 to 5.5 2 20
22P2 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M3.5 0.8 to 1.0 2 to 5.5 3.5 20
24P0 R/L1, S/L2, T/L3, –, +1, +2,
U/T1, V/T2, W/T3
M4 1.2 to 1.5 2 to 5.5 5.5 30

Table of Contents