84
Other Functions Chapter 6-7
Frequency Detection Levels 1 and 2
• The parameter n40 for multi-function output must be set for frequency
detection output.
Set value: 4 for frequency detection level 1 (Output frequency ≥ n58)
Set value: 5 for frequency detection level 2 (Output frequency ≤ n58)
• Set the frequency detection level in n58.
Note The value will be set in 0.1-Hz increments if the frequency is less than 100 Hz
and 1-Hz increments if the frequency is 100 Hz or over.
n58 Frequency Detection Level Changes during
operation
No
Setting
range
0.0 to 400 (Hz) Unit of
setting
0.1 Hz
(see note)
Default setting 0.0
Frequency Detection Level 1
Frequency Detection Level 2
Output
frequency
Frequency
detection level 1
ON
Reset width ±2 Hz
n58 (Frequency
detection level)
Time
Time
Time
Time
ON
ON
n58 (Frequency
detection level)
Output
frequency
Reset width +2 Hz
Frequency
detection level 2