Resistance of Indoor Fan Motor Windings
MODEL CS-A73KR CS-A93KR CS-
A123KR
CONNECTION CWA92288 CWA92296 CWA92290
YELLOW-BLUE 536.5 450.8 457.4
YELLOW-BROWN 77.1 56.9 56.1
BROWN-ORANGE 43.9 74.2 61.2
ORANGE-WHITE 42.7 37.3 25.3
WHITE-RED 111.4 122.6 142.5
Resistance of Outdoor Fan Motor Windings
MODEL CU-A73KR CU-A93KR CU-
A123KR
CONNECTION CWA95245 CWA95381
BLUE-YELLOW 260.5 174.5
YELLOW-RED 446.0 331.0
Resistance of Compressor Windings
MODEL CU-A73KR CU-A93KR CU-A123KR
CONNECTION 2RS122D5AB02 2PS164D3AD02 2KS224D5CA02
C-R 5.627 3.429 2.211
C-S 12.19 4.763 2.924
8. Operation Details
8.1. Cooling Mode Operation
Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
- When the compressor is stopped by Power Switch or Remote
Control, it restarts after 3 minutes when the Power Switch or
Remote Control is turned ON.