Nature of fault Symptom
-Electric current during operation becomes approximately 20% lower than the normal
value.
Insufficient compressing of a
compressor
-The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
-The difference between high pressure and low pressure becomes almost zero.
-Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter.
some cases, a breaker turns off.
Locked compressor
-The compressor is a humming sound.
-Electric current during operation becomes approximately 80% lower than the normal
value.
Insufficient switches of the 4-
way valve
-The temperature different between from the discharge tube to the 4-way valve and from
suction
to the 4-way valve becomes almost zero.