30 minutes Time Saved Control
- The compressor will start automatically if it has stopped for 30
minutes even if the room temperature is below the compressor ON
temperature.
Overload Protection Control
- If the temperature of the indoor heat exchanger rises to 51°C,
Outdoor Fan stops.
The Outdoor Fan restarts when the indoor heat exchanger
temperature falls to 49°C.
- If the indoor heat exchanger becomes 65°C or more, the
compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
Compressor Reverse Rotation Protection Control