8.4. Automatic Mode Operation
1. When the Automatic Mode Operation is selected, the indoor fan
operates at Lo
--
fan speed for 20 second to sense intake air
temperature and determine the 1st operation mode.
2. Operation mode will be determine again after 1 hour of operation,
if the room temperature reaches to set temperature and
compressor off time is over 7 minutes 30 seconds continuously.
The present operation mode will be continued, if the room
temperature does not reach to set temperature (Compressor
keeps running) eventhough after 1 hour from automatic operation
mode started.