No. SX-DSV03335 - 38-
R2.0 Industrial Device Solution Business Unit, Panasonic Corporation
Size G 200 V
Use terminal blocks.
Terminal
No.
(Upper to
bottom)
Control power
input terminal
Main power input
terminal
Regenerative
resistor connecting
terminal
To use an external regenerative resistor (customer prepared), connect an
external regenerative resistor between P and B.
In addition, parameter setting is required for the regenerative resistor.
For details, refer to "Technical Reference - Functional Specification ".
Do not connect anything to the N terminal.
Connect each phase of the motor winding.
U: U phase V: V phase W: W phase
Earth terminal for grounding
External
Dynamic brake
Control connection
· This is a terminal for controlling the electromagnetic contactor (MC) for
external dynamic brake resistor (customer preparation). Please connect if
necessary.
· The applied voltage between DB1 and DB2 must be AC 300 V or less, DC
100 V or less
*Tighten the Earth screw with a torque of M5: 1.8 to 2.0 N · m.
*Tighten the terminal block (control power) screw with a torque of M4: 0.7 to 1.0 N · m.
If the tightening torque exceeds the maximum value, the terminal block may be damaged.
*Tighten the terminal block (main power supply, regenerative resistance, motor) screw with torque of M5: 2.0 to 2.4 N · m.
If the tightening torque exceeds the maximum value, the terminal block may be damaged
* Tighten the fixing screws for the terminal block cover with a torque of M3: 0.19 to 0.21 N · m.
If it exceeds the maximum value of tightening torque, it may be damaged.