6-4
6
Display (functions)
• Usethetemperaturesetting and buttons to change the item code.
Item code Display contents Remarks
00(1) Outdoor unit alarm contents (code): OFF when normal
Blinking8-alarmcodedisplayatpre-trip,LED(2)
Atinitialstatus
01 No. of indoor units connected in that refrigerant system
02 Unit.Nos.ofconnectedindoorunitsinthatrefrigerantsystem*2
03 Operating status of indoor units in that refrigerant system (blinks when alarms occur) *2
04 UnitNos.ofindoorunitsinthatrefrigerantsystemwherethethermostatsareON*2
05 No. of outdoor units connected in that refrigerant system No. of connected
units: 1
06 UnitNos.ofconnectedoutdoorunitsinthatrefrigerantsystem*2
07 Operating status of outdoor units in that refrigerant system (blinks when alarms occur) *2
08
09
0A
0b
0C
0d
0E
0F
10 Totalcompressoroperatingtime(in1-hr.units)*3
11
12
13
14
15
16 Total power ON time of outdoor unit (in 1-hr. units)
17 Compressor start count
18
19
FE Outdoorunitmicrocomputerrmwareversion
FF Outdoor unit microcomputer software version
*Seefollowingpagefor*2and*3.
• XX-YYR.C.
Displays the outdoor unit address of the selected outdoor sub-bus.
XX=Mainbuslineoutdoorsystemaddress(1–30)
YY=Outdoorunitaddressinoutdoorsub-bus(1–8).Thisis“1”
when there is only 1 outdoor unit.
02: <Unit Nos. 1, 2, 3, and 4 are connected>
<Sample displays>
01: <No. of connected indoor units>
4 units connected
Locations where (1), (2), and (3) are displayed
as shown below.
LED
(3)
(1)
(2)
<Sample displays>
01:<No.ofconnectedindoorunits>
4unitsconnected
02:<UnitNos.1,2,3,and4areconnected>
Locationswhere(1),(2),and(3)aredisplayed
as shown below.