7
7-2. List of Simple Setting Items
Item code Item
Setting data
No. Description
FiltersignONtime
(filterlifetime)
0000 Notdisplayed
0001 150hours
0002 2,500hours
0003 5,000hours
0004 10,000hours
0005 Usethefiltercloggingsensor.
Degreeoffilterfouling
0000 Standard(settingattimeofshipping)
0001
Highlyfouled
(FiltersignONtimeisreducedtoone-halfthesettime.)
Centralcontrol
address
0001 Centralcontroladdress1
0002 Centralcontroladdress2
0003 Centralcontroladdress3
0064 Centralcontroladdress64
0099 Nocentralcontroladdressset(settingattimeofshipping)
Operatingmode
prioritychange
0000 Normal(settingattimeofshipping)
0001 Priority
Fanspeedwhen
heatingthermostatis
OFF
CompressorON CompressorOFF
0000 Lo1min.,LL3min. LL
0001 Lo LL
0002 LL LL
0004 Lo1min.,LL3min. Lo
0005 Lo Lo
0006 LL Lo
Heatingintake
temperatureshift
0000 Noshift
0001 Shiftsintaketemperature1°Cdown.
0002 Shiftsintaketemperature2°Cdown.
0003 Shiftsintaketemperature3°Cdown.
0004 Shiftsintaketemperature4°Cdown.
0005 Shiftsintaketemperature5°Cdown.
0006 Shiftsintaketemperature6°Cdown.
Electricheater
installation
0000 Noheater
0001 Heaterinstalled
Humidifyingwhen
heaterthermostatis
OFF
0000 No(settingattimeofshipping)
0001 Ye s
Permit/prohibit
automatic
heating/cooling
0000 Permit
0001 Prohibit
Cool-only
0000 Normal
0001 Coolonly(Set“1”foritemcodeOD.)
• Inordertoavoidwaterleakageanddamagetothefan,donotsetforhumidifyingwhenthethermostatisOFF
unlessavaporizinghumidifierisused.
• Considerthedevicepurposeandtypewhenchangingthesettings.Incorrectsettingsmayresultinmalfunction.
• Donotchangeanysettingdatathatdoesnotappearinthislist.
7-3