7
Item code Item
Setting data
No. Description
(1B)
ForcedthermostatON
0000 5minutes
0001 4minutes
Coolingdischarge
temperatureshift
–010
–10
°C
–009
–9
°C
–008
–8
°C
0010 10°C
Heatingdischarge
temperatureshift
–010
–10
°C
–009
–9
°C
–008
–8
°C
0010 10°C
Temperatureshiftfor
cooling/heatingchange
inautoheat/coolmode
0001 ±1°C
0002 ±2°C
0003 ±3°C
0007 ±7°C
(Upperlimit)
(Lowerlimit)
Changetoremote
controltemperature
settingrange
Cooling
0018 18°C(Lowerlimitatshipment)
0019 19°C
0029 29°C
0030 30°C(Upperlimitatshipment)
(Upperlimit)
(Lowerlimit)
Heating
0016 16°C(Lowerlimitatshipment)
0017 17°C
0029 29°C
0030 30°C(Upperlimitatshipment)
(Upperlimit)
(Lowerlimit)
Drying
0018 18°C(Lowerlimitatshipment)
0019 19°C
0029 29°C
0030 30°C(Upperlimitatshipment)
(Upperlimit)
(Lowerlimit)
Autoheat/cool
0017 17°C(Lowerlimitatshipment)
0018 18°C
0026 26°C
0027 27°C(Upperlimitatshipment)
Humidifieroperation
0000 Normal
0001 Ignoreheatexchangertemperatureconditions.
Filter(CN70)input
switching
0000 Filterinput(differentialpressureswitchinput)
0001 Alarminput(fortroubleinputaboutaircleanerorsimilardevice)
0002
Humidifierinput(Operateslinkedwithdrainpumpwhen
humidifierisON.)
Indoorunitelectronic
controlvalve
0000 Present(Settingatshipment)
0002 None
T10terminalswitching
0000
Normal(UsedasoptionalrelayPCBorJEMAstandardHA
terminal.)
0001 UsedforOFFreminder
0002 Firepreventioninput
7-6