1-15
1
1
Outdoor Units U-250PE1E8
KTM-35D-S1, DTN-C532G3H
CM-12
UKV-25D18
UKV-U030E, DC 12 V
STF-0712G
STF-01AI518A1, AC 220-240 V, 50Hz / 60Hz
MODEL No.
Outdoor Unit
Power Transformer
Rated
VAC, HzSource
Secondary
Coil resistance
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
kΩ
Thermistor (Discharge gas sensor): TH5
Resistance
kΩ
Relay (Comp. Magnetic Contactor)
VACCoil rated
VAC, AContact rating
Coil resistance (at 20°C)
Sol-Control-Valve
4 way valve
4 way valve
Electro magnetic coil
Thermal cut off temperature
Sol-control-valve
Magnetic coil
–10°C: 23.7±5% 20°C:6.5±5%
–5°C:18.8±5% 30°C:4.4±5%
0°C: 15.0±5%40°C: 3.1±5%
5°C: 12.1±5%45°C: 2.6±5%
10°C:9.7±5%50°C: 2.1±5%
60°C:12.4±5% 90°C:4.6±5%
70°C:8.7±5%100°C: 3.4±7%
75°C:7.4±5%110°C: 2.5±7%
80°C:6.3±5%120°C: 1.9±7%
85°C:5.3±5%130°C: 1.5±7%
U-250PE1E8