4-2
4
Remote controller sensor is enabled
28℃
Set temp. in remote
controller
28℃28℃
30.0℃
Detected temp. by
sensor
26.5℃27.0℃
30.0℃
Detected temp. by
body sensor
26.5℃27.0℃
30.0℃ 26.5℃27.0℃
Detected temp. by
remote controller
sensor
30.0℃
=30.0
26.5℃
=26.5
Room temp. = temp.
detected by remote
controller sensor
=27.0
27.0℃
T +2.0deg -1.5℃-1.0deg
ON
Thermostat Thermostat
OFF
Thermostat
ON
Remote controller sensor is enabled
20℃
Set temp. in remote
controller
20℃20℃
17.0℃ 21.5℃
Detected temp. by
sensor
21.0℃
21.0℃
Detected temp. by
body sensor
25.5℃25.0℃
17.0℃ 21.5℃21.0℃
Detected temp. by
remote controller
sensor
=17.0
17.0℃ 21.5℃
=21.5
Room temp. = temp.
detected by remote
controller sensor
=21.0
21.0℃
T +3.0deg -1.5℃-1.0deg
Thermostat
ON
Thermostat
OFF
Thermostat
ON
Body sensor is enabled
ON ONOFF
Set temp.
Set temp.
-2.0
+1
+2
(deg)
The thermostat turns OFF when
ON ONOFF
continues in thermostat OFF zone for 3 minutes.
+1
+2
(deg)
-2.0
Room temp.
Cooling
Heating
Room
temp.
Thermostat
Thermostat
Remote sensor is enabled
ON ONOFF
Set temp.
Set temp.
-1.5
+1
+2
(deg)
ON ONOFF
+1
+2
(deg)
-1.5
Room temp.
Cooling
Heating
Room
temp.
Thermostat
Thermostat
①
②
The thermostat does not turn ON 3 minutes after it turns OFF.
③
The thermostat does not turn OFF for 60 minutes during the test run mode. (Forced thermostat ON)
*However, the thermostat turns OFF if an alarm occurs.
T
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 2 2020/01/30 13:58:46