5-2-1-2
5
Check Prior to Auto Address Setting
2
3
Connect the wiring
correctly
* If an outdoor unit displays an alarm, conduct this process after diagnosing the problem.
Has the wiring of the indoor/outdoor been completed?
Is it all connected correctly?
Run the auto address setting.
1-1
Run the auto address setting.
Is the power of the indoor unit(s) and outdoor unit(s) on?
2-1
Be sure that the indoor and outdoor units are connected with
correct combination described in the catalog.
3-4
3-1
Be sure that the detailed setting items are made at factory setting.
Be sure that the indoor and outdoor units are connected
with correct combination written in catalog.
3-3
3-4
3-2
Is the remote control wiring connected with two indoor/outdoor
combinations or more for group control?
Turn on the power of only one system and run auto address setting again. Upon completion of
the auto address setting, turn on the power for the next system and run auto address setting
while still power switched on, units whose auto address setting have completed. (In the case
of multiple systems, run the auto address setting respectively in due order for each system.)
3-3
Power on
2-1
3-1
Correct the connection
Yes
3-2
Yes
Yes
Yes
No
No
No
No
Correct the connection
4-2Yes
4-3Yes
No
No Correct the setting
Installation
4
[ U3, F3 ]
Relocation
and resetting
of address
or setting
related
Indoor/
outdoor
wiring
Address
1
Auto
Factory setting
Item code Item Value
11 0
99
99
99
Indoor unit capacity
Indoor unit address
Group conrol address
System address
12
13
14
For information on the remote control’s detailed settings, refer to the Reference Materials.
4-1
4-2
4-3
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 2 2020/01/29 21:17:40