5-1-1
5
5-1. Contents of Remote Controller Switch Alarm Display
Failure in receiving serial
signal from remote controller's
indoor unit
Failure in indoor unit receiving
serial signal from outdoor unit
Duplication of indoor unit address
Duplication of main remote
controller setting
Improper setting
Settings of system address,
indoor unit address and group
control are not made
Setting failure of nonvolatile
memory IC
Failure in indoor unit serial
signal from remote controller
Automatic address alarm
Communication error between
main and sub indoor units
Group control wiring is connected
to individual control indoor unit
E01
E02
E03
E04
E08
E09
E12
E14
E15
E16
E24
E29
E18
L03
L07
L08
L09
Error in indoor unit receiving signal from remote controller (central)
Faulty remote controller
Disconnection/Contact failure of remote controller wiring
CHK(check) pins on the indoor unit control PCB are short circuited
Faulty remote controller
Faulty setting of EEPROM (IC010) on indoor unit
In the case of non-group control:
Power supply OFF of outdoor unit
Disconnection / Contact failure of inter-unit wiring
In the case of group control:
Automatic address operation was not carried out.
Wrong wiring of remote controller
Disconnection / Contact failure of inter-unit wiring
Faulty indoor unit control PCB
Faulty outdoor unit control PCB
Communication circuit fuse (F302) on indoor unit control PCB opened
Duplication of indoor unit address setting
Error because of more than one remote controller setting to main
Automatic address setting start is prohibited
Duplication of main unit in group control
The total capacity of indoor units is too low
The total capacity of indoor units is too high
The numbers of indoor units is two or more.
Disconnection of wiring between main unit and additional units
Contact failure of wiring
Faulty indoor unit control PCB (Main or Addition)
Duplication of main indoor unit address in group control
Group control wiring is connected to individual control indoor unit
Indoor unit address is not set
Indoor & outdoor unit type
miss-matched
Duplication of group control's
main indoor unit
Indoor unit capacity is not set
Fuse on outdoor unit control PCB opened
Since failure of an outdoor fan motor is considered as a cause,
both outdoor unit control PCB and outdoor unit fan motor are
exchanged simultaneously.
Outdoor unit Communication error
Outdoor unit Communication error
Serial
communication
errors
Missetting
Continued
Setting error, indoor/outdoor unit type/model miss-matched
4-way valve locked trouble / operation failure
L02
L18
ON:
Operation
Standby
Blinking: OFF:
Possible cause of malfunction
Wireless
remote controller
receiver display
Wired
remote
control
display
Timer
Operating lamp
blinking
Operating lamp
blinking
Standby
lamp blinking
Standby
lamp blinking
Operating and
Standby
lamps blinking
simultaneously
Operating and
Standby
lamps blinking
simultaneously
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 1 2020/01/29 21:17:40