5-2-2-10
5
H03 Outdoor Current Transformer
Malfunction Decision Conditions
operating at certain frequency value for 3 minutes.
An input current, detected by Current Transformer CT, is below threshold value when the compressor is
Malfunction Caused
Lack of gas
Broken CT (current transformer)
Broken Outdoor PCB
Troubleshooting