5-2-2-18
5
P29 Compressor Rotation Failure
Malfunction Decision Conditions
detection circuit.
Malfunction Caused
A compressor rotation failure is detected by checking the compressor running condition through the position
Faulty Outdoor PCB
Compressor terminal disconnect
Faulty compressor
Troubleshooting
5-3. Inspection of Parts (Outdoor Unit)
(1) Electronic control valve (MOV1)
Set the tester to the 12 V range; if the value displayed is approximately 4 V, then the voltage is normal.)
If the voltage is normal, measure the resistance between connector pin 5 and pins 1 through 4.
Resistance between pin 5 and pins 1 through 4 should be approximately 46 Ω for all. (If the result is 0 Ω or,
then replace the coil.)
(2) Outdoor Unit Fan Motor
Model No. Part No. (Panasonic) Part No.
U-36PZ3E5
U-50PZ3E5
U-60PZ3E5
U-71PZ3E5
L6CAYYYL0064
L6CAYYYL0064
L6CAYYYL0076
L6CAYYYL0076
NFD-52FV-D840-16
NFD-52FV-D840-16
NFD-62FV-D840-6
NFD-62FV-D840-6
(3) Coil Resistance of Compressor
Model No.
Part No.
(Panasonic)
Part No.
Inverter compressor (at 20°C)
U - V V - W U - W
U-36PZ3E5
U-50PZ3E5
U-60PZ3E5
U-71PZ3E5
ACXB09-03470
ACXB09-04960
ACXB09-04940
ACXB09-04950
9RS102XFA21
9RD132XAB21
9RD132XAA21
9KD240XBA21
1.211
1.897
1.897
0.720
1.211
1.882
1.882
0.708
1.211
1.907
1.907
0.726
STM/STM1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN-STM/CN-STM1 connector
(white)