1-1. Unit Specifications
PZ3
2. Middle Static Pressure Duct Type S-6071PF3E(60) / U-60PZ3E5
INDOOR MODEL S-6071PF3E(60) - -
PANEL MODEL - - -
OUTDOOR MODEL - U-60PZ3E5 -
Branch pipe MODEL -
Performance test condition ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 1Ø 50Hz
V 220V 230V 240V 220V 230V 240V Min Max
C
O
O
L
I
N
G
Capacity
kW 5.7 5.7 5.7 - - - 2.0 6.3
BTU/h 19400 19400 19400 - - - 6800 21500
Current A - - - 7.45 7.15 6.85 - -
Input power
W - - - - - - - -
TOTAL W - 1.610k 1.610k 1.610k 0.340k 2.400k
Annual consumption TOTAL kWh *
4
- - - - 805 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.54 3.54 / A 3.54 5.88 2.63
ErP
*
6
Pdesign kW - - - - 5.7 - - -
SEER (W/W) - - - - 6.4 - - -
Annual consumption
kWh - - - - 310 - - -
Class - - - - A++ - - -
Power factor % - - - 98 98 98 - -
Noise indoor
*
7
dB-A (H/M/L) 30 / 26 / 23 - - -
Power Level dB 53 / 49 / 46 - - -
Noise outdoor
dB-A (H/L) - 47 / - - -
Power Level dB - 64 / - - -
H
E
A
T
I
N
G
Capacity
kW 5.7 5.7 5.7 - - - 1.8 7.0
BTU/h 19400 19400 19400 - - - 6100 23900
Current A - - - 6.55 6.25 6.00 - -
Input power
W - - - - - - - -
TOTAL W - 1.410k 1.410k 1.410k 0.290k 2.480k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 4.04 4.04 / A 4.04 6.21 2.82
ErP
*
6
Pdesign at -10°C
kW - - - - 4.4 - - -
Tbivalent °C - - - - -10 - - -
SCOP (W/W) - - - - 4.4 - - -
Annual consumption
kWh - - - - 1376 - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - A+ - - -
Power factor % - - - 98 98 98 - -
Noise indoor
*
7
dB-A (H/M/L) 30 / 26 / 23 - - -
Power Level dB 53 / 49 / 46 - - -
Noise outdoor
dB-A (H/L) - 48 / - - -
Power Level dB - 65 / - - -
LOW TEMP
Total capacity(kW) / Input power(W) / COP
- - - - -
EXTRA LOW TEMP
Total capacity(kW) / Input power(W) / COP
- - - - -
Max Current(A) / Max Input power(W) - - - 13.1 / 2.60k 13.1 / 2.65k 13.1 / 2.70k -
Starting current(A) (Cooling/Heating) - - - 7.45 / 6.55 7.15 / 6.25 6.85 / 6.00 -
Comp output(W) - 1.70k 1.70k 1.70k -
Time Delay fuse max size(A) - 20 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 165 40 -
Moisture removal volume L/h 1.7 (1.7 ×1) - -
External static pressure
Pa 30 (MIN10 - MAX150) - -
Indoor
Air ow
*
7
Cooling m³/min (H/M/L) 21.0 / 19.0 / 15.0 - - -
Heating m³/min (H/M/L) 21.0 / 19.0 / 15.0 - - -
Outdoor
Air ow
Cooling m³/min - 42.6 - -
Heating m³/min - 41.5 - -
Refrigerant type / amount(ship) k
g
/ amount(max) k
g
- R32 1.150 1.490 -
F-Gas
GWP /
CO2eq (ton) (PRECHARGED AMOUNT) /
CO2eq (ton) (MAXIMUM CHARGED AMOUNT)
- 675 0.78 1.01 -
Product dimension
Height mm 250 695 -
Width mm 1000 875 -
Depth mm 730 320 -
Product dimension (Panel) H×W×D mm
-
- -
Packing dimension
Height mm 805 761 -
Width mm 1265 1049 -
Depth mm 340 460 -
Weight
(NET) k
g
30 42 -
(GROSS)
k
g
36 46 -
Panel (NET)
k
g
- - -
Layers limit (actually) 3 (4) 3 (4) -
Operation condition
Cool (DBT) 18°C ~ 32°C -10°C ~ 43°C -
Heat (DBT) 16°C ~ 30°C -15°C ~ 24°C -
Max Working Pressure HP/LP MPa 4.15 / 2.55 -
P
I
P
I
N
G
Pipe port diameter mm (inch) (Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8) (Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) -
Pipe diameter mm (inch)
(Liquid)Ø6.35(1/4) (Gas)Ø12.7(1/2) *Connect the gas socket tube(Ø15.88-Ø12.7) to the gas tubing side indoor unit
*Connect the liquid socket tube(Ø9.52-Ø6.35) to the liquid tubing side indoor unit
-
Connecting method ared type ared type -
Standard length m
5 m -
Pipe length range m 3 ~ 30 m -
Indoor unit & Outdoor unit height dierence m 15 m(OD located lower) / 15 m(OD located higher) -
Add gas amount
g
/m 15
g
/m -
Pipe length for additional gas m 7.5 m -
* In the case of standard installation (Horizontal installation in the celling, rear side air intake)
* In the case of nanoe X OFF
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2 If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6
SEER and SCOP classication is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season, Other che data indicates in an attached sheet.
*7 H: High at setting 5 stage (Level 5), M: Middle at setting 5 stage (Level 3), L: Low at setting 5 stage (Level 1) Noise of L is indicated by the values at FAN mode
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 3 20/01/30 10:24:32