CAUTION ON INSTALLATION
Criteria for Human Detection Area
•
A place where the blind angle of the Human Detection Sensor cannot detect human.
nstall the panel for cassette (ECONAVI type) so that human motion can be detected.
•
If there is a heat source or cooling unit in the detection area, the sensor cannot occasionally detect properly.
•
The Floor Temperature Sensor detects within the sensor area of Human Detection Sensor.
Human Detection Sensor
Floor Temperature Sensor
Detection area of Human Detection Sensor
1 m above floor visual range
Installation
height:
2.7 - 5 m
Detection area of Floor Temperature Sensor
Approx. ø7 - 9 m
Criteria of human detection sensor area
Installation height of indoor unit 2.7 m : Approx. ø7 m
Installation height of indoor unit 4 m : Approx. ø8 m
Installation height of indoor unit 5 m : Approx. ø9 m
Do not install at the following locations. (Cause of trouble and malfunction)
• Humid, oily, frequent vibration
• Direct sunlight and near by heat source
• Frost
Panel for Cassette (ECONAVI type)
CZ-KPU3A, CZ-KPU3AW
Applicable indoor unit : 4-Way Cassette