1
1-11-1-1-22
Others
Setting No.
(1)
Remote controller
setting data
Item code 5d
0001
Contents &
optional parts name
Air-flow blocking kit
(for 3-way air flow)*
2
1
High-ceiling setting 1*
2
(3) 0003
High-ceiling setting 2*
2
(6)
Air-flow blocking kit
(when a duct is
connected.)
0006
Air-flow blocking kit
(for 2-way air flow)*
2
oN gnittes tnereffid ni strap lanoitpo gnisu nehW 1* . in
combination with multiple units, conform it to the larger
setting No.
)m( thgieh gnilieC 2*
(1) Checking After Installation
1) Check that there are no gaps between the unit and the
panel for cassette, or between the panel for cassette
and the ceiling surface.
* Gaps may cause water leakage and condensation.
.detcennoc yleruces si gniriw eht taht kcehC )2
ton lliw palf otua eht ,detcennoc yleruces ton si ti fI *
operate.
(“P09” is displayed on the remote controller.)
In addition, the water leakage and condensation may
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section “Wireless
Signal Receiver” in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way Cassette)
Check the optional parts accordingly in the following
table.
Table for DC Fan Motor Tap Settings*
Indoor unit type
Standard
High-ceiling setting 1
(factory setting)
High-ceiling setting 2
Air-flow blocking kit
(for 3-way air flow)
3.0
3.3
3.6
3.8
4.2
S-3650PU3E S-6071PU3E
2.7
3.2
3.5
Air-flow blocking kit
(for 2-way air flow)
3.8
4.2
eht no gnittes nehW )1 P.C. Board
Setting No. DIP switch
<Procedure>
Stop the system before performing these steps.
1
oc xob tnenopmoc lacirtcele eht nepO ver, then
check the indoor unit control PCB.
2
lortnoc tinu roodni eht no hctiws PID eht egnahC
Setting No. DIP switch
(1)
PCB in accordance with the setting number which
was confirmed in “Table for DC Fan Motor Tap
Settings”.
TP6
TP3
TP1
ON
1 2 3
(6)
ON
TP6
1 2 3
TP3
TP1
(3)
ON
TP6
1 2 3
TP3
TP1
<Procedure of CZ-RTC5B>
Stop the system before performing these steps.
1
Keep pressing the
, and buttons
simultaneously for 4 or more seconds.
The “Maintenance func” screen appears on the LCD
display.
2
Press the or button to see each menu.
press the
button.
If you wish to see the next screen instantly, press the
or button.
Select “8. Detailed settings” on the LCD display and
The “Detailed settings” screen appears on the LCD display.
Maintenance func
Sel.
20:30 (THU)
Page [ ] Confirm
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Maintenance func
6. Servicing check
5. Sensor info.
Sel.
20:30 (THU)
7. Simple settings
8. Detailed settings
Page [ ] Confirm
TP6
TP3
TP1
1
ON
2 3
TP6
TP3
TP1
1 2 3
SW001
Indoor unit control PCB
Setting example
1: OFF
2: OFF
ON
3: ON
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 22 20/01/30 10:25:16