20
Magellan & Spectra SP • Installation Guide
Fire Circuits
When a zone is programmed as a fire zone, the zone becomes normally open and requires an EOL resistor. If a line short occurs or if the smoke detector becomes
active, whether the system is armed or disarmed, the control panel will generate an alarm. If a trouble occurs on a fire zone, the Fire Loop Trouble will appear in the
keypad’s trouble display (See “Trouble Display” on page 63) and the control panel can transmit the Fire Loop Trouble report, if programmed, in section [866].
Figure 5: Fire Circuits
4-Wire and 2-Wire Installation:
For 4-wire installation, program the Activation Event so that the smoke detectors can be reset by pressing the [CLEAR] + [ENTER] keys for three seconds. See Event
Group # 6 in the Event Description list in the programming guide.
For 2-wire smoke detector installation, connect the 2-wire smoke detectors. If a line short occurs or the smoke detector activates, whether the system is disarmed,
the control panel will generate an alarm. If the line is open, the “Zone Fault” trouble indication appears on the trouble display and the report code is sent to the
monitoring station, if programmed. To reset 2-wire smoke detectors, press the [
CLEAR] + [ENTER] keys for three seconds.

Table of Contents

Other manuals for Paradox SP6000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox SP6000 and is the answer not in the manual?

Paradox SP6000 Specifications

General IconGeneral
Partitions2
User Codes32
Event Buffer256 events
PGM Outputs2 (expandable to 16)
CompatibilityCompatible with wireless expansion modules and keypads
CommunicationPhone line, GSM, IP
Users32
ZonesUp to 32 (5 on-board)
KeypadsSupports multiple keypad types

Related product manuals