Tamper Supervision on Panel (MG5075 only)
Section [700]: Supervision Options
Option [8] OFF= Panel tamper supervision disabled
Option [8] ON= Panel tamper supervision enabled (default)
When the control panel detects a tamper, the control panel can generate an alarm or trouble, unless the Tamper Supervision is disabled.
Keypad Panic Options
Section [702]: General Options
Option [1] OFF= Panic 1 Disabled (default)
Option [1] ON = Panic 1 Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by option [4].
Option [2] OFF= Panic 2 Disabled (default)
Option [2] ON = Panic 2 Enabled
Pressing the [4] and [6] keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by option [5].
Option [3] OFF= Panic 3 Disabled (default)
Option [3] ON = Panic 3 Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 3 seconds will generate a silent or audible alarm as defined by option [6].
Option [4] OFF= Panic 1 is Silent (default)
Option [4] ON = Panic 1 is Audible
Option [5] OFF= Panic 2 is Silent (default)
Option [5] ON = Panic 2 is Audible
Option [6] OFF= Panic 3 is Silent (default)
Option [6] ON = Panic 3 is Audible
Silent alarm:
The control panel emits a confirmation beep and transmits the appropriate Panic report code if programmed in section [863]. The control panel will not enable the
keypad buzzers or the control panel’s
BELL output (no audible alarm).
Audible alarm:
Same as silent alarm, except the keypad buzzers and the BELL output will activate until a user cancels the alarm (disarms) with a valid user access code or when the
Bell Cut-Off Timer elapses (See “Bell Cut-Off Timer” on page 47).
Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1.
Panic Lockout Timer
Section [718]
When a panic alarm is activated, the control panel can ignore the disarm signal from a remote control for a specified period. This prevents an aggressor from
disarming the system by remote control during a panic situation. In section [718] enter a 3-digit value (000 to 255, 000 = disabled) representing the number of
seconds that the remote controls will be locked out of the system.
Flex-Instant Delay
Section [720]
The Flex-Instant Delay is used to prevent false alarms when the premises is Stay/Sleep armed. In section [720] enter a 3-digit value (000 to 255, 000 = disabled)
representing the number of seconds that the panel will delay an alarm allowing you to disarm the system (default 15 seconds).