Programming Your Application
6-9
650V AC Drive
MMI Parameters Table
Display Parameter Description Range Default
SET::TRIP Menu
DISABLE LOOP Disables LOST I LOOP trip (4-20mA) 0= TRIP ENABLED
1= TRIP DISABLED
1
AIN2 OVERLOAD Disables the overload trip (Terminal 3) As
S
LOOP 0
DISABLE STALL Disables STALL trip As
S
LOOP 0
DISABLE MOTOR
OVERTEMP
Disables the motor thermistor trip As
S
LOOP 0
INVERSE TIME Disables the inverse time trip As
S
LOOP 1
DYNAMIC BRAKE
RESISTOR
Disables the dynamic brake resistor trip As
S
LOOP 1
DYNAMIC BRAKE
SWITCH
Disables the dynamic brake switch trip As
S
LOOP 1
SPEED FEEDBACK Disables the speed feedback trip As
S
LOOP 0
OVERSPEED Disables the overspeed trip As
S
LOOP 0
DISPLAY
(KEYPAD)
Disables the display (keypad) trip As
S
LOOP 0
DC LINK RIPPLE
F
Disables the DC link ripple trip As
S
LOOP 0
SET::SERL Menu
REMOTE COMMS
SEL
F
Selects the type of remote communications mode:
0 : FALSE, and in REMOTE mode then control is
from the terminals.
1 : TRUE, and in REMOTE mode then control is
from the communications.
0=FALSE
1=TRUE
0
COMMS
TIMEOUT
F
Sets the maximum time allowed between
refreshing the COMMS COMMAND parameter.
The drive will trip if this time is exceeded. Set the
time to 0.00 seconds to disable this feature.
0.0 to 600.0s 0.0s
COMMS
ADDRESS
F
The drives identity address.
Note: if set to 0, it will only respond to broadcast
messages.
0 to 255 0
BAUD RATE
F
Selects the Baud Rate for the MODBUS protocol. 0 : 1200
1 : 2400
2 : 4800
3 : 7200
4 : 9600
5 : 14400
6 : 19200
7 : 38400
8 : 57600
4
PARITY
F
Selects the Parity for the MODBUS protocol. 0= NONE
1= ODD
2= EVEN
0
REPLY DELAY ms The time in milliseconds between the drive
receiving the complete request from the
communications master (PLC/PC) and replying to
this request.
0 to 200 5
OP PORT
PROTOCOL
F
Selects the protocol to be used by the keypad port
on the front of the drive. When EIBISYNC ASCII is
selected, BAUD RATE is 19200 and PARITY is
EVEN. FIELDBUS is reserved for future use.
0= AUTOMATIC
1= KEYPAD
2=EIBISYNC ASCII
3= MODBUS
4= FIELDBUS
0
P3 PORT
PROTOCOL
F
Selects the protocol to be used by the RS232
programming port on the drive's control board.
When EIBISYNC ASCII is selected, BAUD RATE is
19200 and PARITY is EVEN. FIELDBUS is reserved
for future use.
As
S
SE07 0