6-10 Programming Your Application
650V AC Drive
MMI Parameters Table
Display Parameter Description Range Default
SET::SETP Menu
JOG ACCEL TIME As
P
4, for Jog 0.0 to 3000.0s 1.0
JOG DECEL TIME As
P
5, for Jog 0.0 to 3000.0s 1.0
RAMP TYPE Selects the ramp type 0=LINEAR
1=S
0
S RAMP JERK Rate of change of acceleration of the curve in units
per second³
0.01 to 100.00 s3 10.00
S RAMP
CONTINUOUS
When TRUE and the S ramp is selected, forces a
smooth transition if the speed setpoint is changed
when ramping. The curve is controlled by the S
RAMP JERK parameter. When FALSE, there is an
immediate transition from the old curve to the new
curve
0=FALSE
1=TRUE
1
MIN SPEED
MODE
Selects a mode to determine how the drive will
follow a reference: Proportional : minimum limit,
Linear : between minimum and maximum.
0=PROP.W/MIN.
1=LINEAR (used by
the 601 product)
0
SKIP FREQUENCY
1
This parameter contains the centre frequency of
skip band 1 in Hz
0.0 to 240.0 Hz 0.0
SKIP FREQUENCY
BAND 1
The width of skip band 1 in Hz 0.0 to 60.0 Hz 0.0
SKIP FREQUENCY
2
This parameter contains the centre frequency of
skip band 2 in Hz
0.0 to 240.0 Hz 0.0
SKIP FREQUENCY
BAND 2
The width of skip band 2 in Hz 0.0 to 60.0 Hz 0.0
AUTO RESTART
ATTEMPTS
Determines the number of restarts that will be
permitted before requiring an external fault reset
0 to 10 0
AUTO RESTART
DELAY
Determines the delay between restart attempts for
a trip included in AUTO RESTART TRIGGERS and
AUTO RESTART TRIGGERS+. The delay is
measured from all error conditions clearing
0.0 to 600.0 s 10.0
AUTO RESTART
TRIGGERS
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF 0x0000
AUTO RESTART
TRIGGERS+
Allows Auto Restart to be enabled for a selection of
trip conditions.
Refer to Chapter 6: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF 0x0000
DB ENABLE Enables operation of the dynamic braking. 0=FALSE
1=TRUE
1
DB RESISTANCE The value of the load resistance. 1 to 1000 product
code
dependent
DB POWER The power that the load resistance may continually
dissipate.
0.1 to 510.0 kW product
code
dependent
DB OVER-RATING Multiplier that may be applied to DB POWER for
power overloads lasting no more than 1 second.
1 to 40 25
TORQUE
FEEDBACK
Shows the estimated motor torque, as a
percentage of rated motor torque.
.xx % .xx %
TORQUE LEVEL This parameter sets the value of load at which AT
LOAD becomes TRUE. AT LOAD is selectable by
the digital inputs. Refer to
S
OP21 and
S
OP31.
100% = rated torque for the motor.
-300.0 to 300.0 % 100.0 %
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN +46 (0)18-65 70 00 +46 (0)18-10 74 78 info@regal.se www.regal.se