EasyManua.ls Logo

Parker ac890 - Page 107

Parker ac890
711 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-25 890SD Standalone Drive
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
11
B
D
USER 24V DC INPUTS
Name Range Description
X13
01
24V INPUT
24V DC
User +24V (2A per unit)
Functionality only available
when used in frames B, C & D.
02
24V INPUT
24V DC
User +24V (2A per unit)
03
0V INPUT 0V 0V (24V) input
04
0V INPUT
0V
0V (24V) input
Note These connections are not necessary for normal operation of the drive.
Following paragraphs are only valid when the control card is used on frames B, C & D:-
Connection can be made from a suitable, external 24V source. This 24V DC control supply allows for
configuration and commissioning of the system without the AC supply being present. The drive will
operate with this supply but will not turn a motor.
Connection is not required when the AC supply is present, but the connection can be safely left connected.
You can connect up to four 890SD units in total when daisy-chaining 24V using these terminals (8A
maximum). If you have more than four 890SDs, use a 24V rail and wire as shown in the Wiring Diagram
on page 5-11.

Table of Contents