D-193
Programming  
890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D 
1Parameter Table:  PREF Number Order 
2PREF  Name  Block  Type  Range  Default  ro\rw  Notes 
1.03  TYPE  ANALOG INPUT 1  ENUM  0 : -10..+10 V 
1 : 0..+10 V 
-10..+10 V  rw   
1.06  VALUE  ANALOG INPUT 1  REAL  _.x  100.0 %  ro   Output 
2.03  TYPE  ANALOG INPUT 2  ENUM  0 : -10..+10 V 
1 : 0..+10 V 
-10..+10 V  rw   
2.06  VALUE  ANALOG INPUT 2  REAL  _.x  100.0 %  ro   Output 
3.03  TYPE  ANALOG INPUT 3  ENUM  0 : -10..+10 V 
1 : 0..+10 V 
2 : 0..20 mA 
3 : 4..20 mA 
-10..+10 V  rw   
3.04  BREAK ENABLE  ANALOG INPUT 3  BOOL  0 : FALSE 
1 : TRUE 
FALSE  rw   
3.05  BREAK VALUE  ANALOG INPUT 3  REAL  -300.00 to 300.00 %  0.00 %  rw   
3.06  VALUE  ANALOG INPUT 3  REAL  _.x  100.0 %  ro   Output 
3.07  BREAK  ANALOG INPUT 3  BOOL  0 : FALSE 
1 : TRUE 
FALSE  ro   Output 
4.03  TYPE  ANALOG INPUT 4  ENUM  0 : -10..+10 V 
1 : 0..+10 V 
2 : 0..20 mA 
3 : 4..20 mA 
-10..+10 V  rw   
4.04  BREAK ENABLE  ANALOG INPUT 4  BOOL  0 : FALSE 
1 : TRUE 
FALSE  rw   
4.05  BREAK VALUE  ANALOG INPUT 4  REAL  -300.00 to 300.00 %  0.00 %  rw   
4.06  VALUE  ANALOG INPUT 4  REAL  _.x  100.0 %  ro   Output 
4.07  BREAK  ANALOG INPUT 4  BOOL  0 : FALSE 
1 : TRUE 
FALSE  ro   Output 
5.06  VALUE  ANALOG INPUT 5  REAL  _.x  0.0 %  ro   Output